Our advancement depends over the superior machines, exceptional talents and continually strengthened technology forces for Three-Phase Voltage And Current Collector , Smart Life Energy Monitoring , Power Meter Single Phase , Welcome any inquiry to our company. We will be glad to establish friendly business relationships with you!
Newly Arrival Wireless Power Meter - JSY-MK-138 12 channel mutual inductance electric energy metering module – JIAN SI YAN Detail:

Description

Jsy-mk-138 12 way mutual inductance electric energy metering module can be widely used in energy-saving transformation, electric power, communication, railway, transportation, environmental protection, petrochemical, steel and other industries to monitor the current and power consumption of AC equipment.

Technical Parameter

1. Single phase AC input
1) Voltage range: 100V, 220V, 380V, etc.
2) Current range: 5A, 50a, 100A, etc; The model of external opening current transformer is optional.
3) Signal processing: special metering chip is adopted, and 24 bit AD is adopted.
4) Overload capacity: 1.2 times the range is sustainable; The instantaneous (<20ms) current is 5 times, the voltage is 1.2 times, and the range is not damaged.
5) Input impedance: voltage channel >1k Ω /v.

2. Communication interface
1) Interface type: 1-way RS-485 communication interface.
2) Communication protocol: MODBUS-RTU protocol.
3) Data format: software can set “n, 8,1″, “E, 8,1″, “O, 8,1″, “n, 8,2″.
4) Communication rate: the baud rate of RS-485 communication interface can be set to 9600, 19200, 38400bps; The baud rate defaults to 9600bps.

3. Test output data
Voltage, current, power, electric energy and other electrical parameters.

4. Measurement accuracy
Voltage, current and power: ± 1.0%; Active kwh is level 1.

5. Electrical isolation
RS-485 interface is isolated from AC power supply, voltage input and current input; Isolation withstand voltage 2000vac.

6. Power supply
1) Two power supply modes are selected: take power from the input AC phase C, and note that the voltage range is ac85~265; DC power supply can also be selected, and the input range is +9v~15v.
2) Typical power consumption: ≤ 1W.

7. Working environment
1) Working temperature: -20~+70 ℃; Storage temperature: -40~+85 ℃.
2) Relative humidity: 5~95%, no condensation (at 40 ℃).
3) Altitude: 0~3000 meters.
4) Environment: a place without explosion, corrosive gas and conductive dust, and without significant shaking, vibration and impact.

8. Temperature drift
≤100ppm/℃

9. Installation method
The distance between screw fixing and installation holes is 105*58.5mm

10. Product size
268*84*46mm


Product detail pictures:

Newly Arrival Wireless Power Meter - JSY-MK-138 12 channel mutual inductance electric energy metering module – JIAN SI YAN detail pictures


Related Product Guide:

We are proud of the high customer satisfaction and wide acceptance due to our persistent pursuit of high quality both on product and service for Newly Arrival Wireless Power Meter - JSY-MK-138 12 channel mutual inductance electric energy metering module – JIAN SI YAN, The product will supply to all over the world, such as: Mauritania, New Zealand, Johannesburg, We hope to have long-term cooperation relationships with our clients. If you are interested in any of our products, please do not hesitate to send enquiry to us/company name. We ensure that you can be totally satisfied with our best solutions!
  • The quality of the products is very good, especially in the details, can be seen that the company work actively to satisfy customer's interest, a nice supplier.
    5 Stars By Lisa from Danish - 2018.10.31 10:02
    Reasonable price, good attitude of consultation, finally we achieve a win-win situation,a happy cooperation!
    5 Stars By Irma from Sao Paulo - 2018.10.01 14:14

    RELATED PRODUCTS