Intelligent PDU Modules

IP PDU Modules for Network Remote Monitoring and Management Power Distribution System

ip pdu component
  1. 1. Introduction
  • Professional-grade network remote monitoring and management power distribution system is the latest scientific research achievement in the field of power distribution technology after years of dedicated research. This product is based on the development trend of the world's future power distribution monitoring and management technology, combined with the technical requirements of the modern data center application environment, and adopts the latest core technology with completely independent intellectual property rights, as well as network communication, power distribution, and electric energy metering technologies to design the latest network remote monitoring and management power distributor.
  • This device refers to the following standards:
  • Q/GDW 1354-2013 "Smart Electricity Meter Functional Specifications".
  • GB/T 17626.2-1998 Electromagnetic compatibility test and measurement technology - Electrostatic discharge immunity test. GB/T 17626.3-1998 Electromagnetic compatibility test and measurement technology f- Radio frequency electromagnetic field radiation immunity test . GB/T 17626.4-1998 Electromagnetic compatibility test and measurement technology - Electrical fast transient pulse group immunity test . GB/T 17626.5-1998 Electromagnetic compatibility test and measurement technology - Surge (impact) immunity test . GB/T 17626.8-1998 Electromagnetic compatibility test and measurement technology - Power frequency magnetic field immunity test .
  • MODBUS-RTU communication protocol.

2. Product Introduction

  • 2.1  Product Overview
  • Single-phase and three-phase smart PDU meters are based on the innovative SUM (sustainable, scalable and maintainable) design concept technology. As a key component of the metering cabinet power distribution unit (PDU), after being installed into the main body of the PDU, it can Provides active metering capabilities for energy optimization and circuit protection. User-set alarm thresholds can effectively reduce risks by warning of potential circuit overloads through real-time local and remote alarms. Metered rack PDUs provide power usage data to support data center managers in making informed decisions about load balancing and proper IT sizing, thereby significantly reducing total cost of ownership. Users can configure metered cabinet PDU via Ethernet access or RS485. This series of products can be widely used in data center rooms such as IDC, banks, securities, governments, and enterprises.

2.2  Function introduction

Performance parameters

Technical indicators

Electrical parameters

Input

Optional

Single Phase

Input voltage 176-264V
Maximum total load current 63A

Three-phase

Input voltage 3*220V 50/60HZ
Maximum total load current 3*32A Optional 63A, 120A, 150A
Output Output Voltage 176-264V
Output Current 8A, optional high current 20A
Output Port Optional, up to 36 ports
Frequency 50/60Hz

User interface

Display TFT color screen
Operation buttons Up, down, set, reset buttons
Communication interface One Ethernet, two RS485
Temperature and humidity interface Two
Switch input interface Two interfaces, 4 channels
Switch output interface One interface,channels

Electrical parameter measurement

PDU total measurement Voltage, current, power, electric energy
Each output measurement Voltage, current, power, electric energy
Each output can be remotely turned on/off Yes
Customize the power-on/power-off sequence and interval time for each output Yes
Administrator permissions can be defined in different levels Yes
Customize alarm signal thresholds Voltage and current adjustable
Cascade function Yes, 4 products can be cascaded

Monitoring function

Load current monitoring
Load power monitoring
Voltage monitoring
Power monitoring
Ambient temperature and humidity monitoring

Setting the function

Load current upper and lower limit settings
Ambient temperature and humidity upper and lower limit settings
Email alert address settings
SNMP (V1, V2c,V3) settings
Network parameter settings (IP, gateway, mask, DNS )

Alarm function

system

Alerts

When the load current exceeds the rated value
When the temperature and humidity exceed the limit

Custom

Alerts

When the load current exceeds the rated value
When the temperature and humidity exceed the limit

Alerts

Way

Buzzer beeps
LCD value flashes
Automatically send an email to the system administrator
SNMP sends Trap alarm status information
Serial communication background sends alarm status information
Access method WEB access and control through IE
SNMP (V1,V2c,V3) access and control via standard network management workstation
User Management User ID and password settings
environment Operating temperature -20 ~ 60℃
Extreme operating temperature -30 ~ 70℃
Relative humidity 10 ~ 90%
Storage and transportation temperature limit -40 ~ 70℃

 

2.3  Model selection

  • ◆ MK-352 IP stands for intelligent PDU meter head.
  • ◆ JSY-MK-352AFE  stands for three-phase four-wire power module.
  • ◆ JSY-1073 stands for single-phase power module.
  • ◆ JSY-1054 stands for 4-channel relay control module, current specification: 8A (maximum 16A).
  • ◆ JSY-1084 indicates 4-channel relay control module, current specification: 20A ( maximum 50A ).

3. Main functions

3.1 Real-time monitoring function

  • The display screen can view the monitored total load current, total voltage, total power, total electric energy, power factor, and load current parameters of each independent unit: the content displayed on the LCD screen can be viewed on the Web page, and the closed/open state of each independent unit, temperature/humidity sensor data and operating status can be controlled. 4-channel switch input can be configured by the customer, and there are 2-channel switch output.

3.2 Socket unit control

  • ◆ Control the closing and opening of a single relay, or control multiple relays simultaneously.
  • ◆ You can set the sequential delay power-on, up to 6 seconds. (This means that when two or more channels are controlled continuously, after the previous channel is completed, you need to wait 6 seconds before the next channel starts to operate.)
  • ◆ Each relay can be set to start at a fixed time and date.

3.3 Customized alerts

  • ◆ The total load current/voltage over-limit threshold can be customized, the load current over-limit threshold of each socket unit can be customized, and the temperature/humidity over-limit threshold can be customized.
  • ◆ The buzzer sounds. an email is sent to the system administrator. SNMP sends a trap alarm status information.

3.4 Master-slave (cascade) communication

  • The two interfaces are the same RS485 communication bus, providing two interfaces for easy cascading. RS485 communication cascade can connect up to 4 instruments. Communication cables can use ordinary shielded twisted pair cables. When RS485 communication cables are routed outdoors, attention should be paid to the grounding of the cable shielding layer. The total length of the communication cable should not exceed 1200 meters. The positive and negative polarities of the RS-485 ports of each device must be connected correctly. If the shielded twisted pair cable is long, it is recommended to connect a 120 Ω resistor at the end and reduce the transmission rate to improve the reliability of communication.
master-slave cascade setup
  1. 4. Technical parameters and installation

4.1 User interface and parameters

pdu meter

Note: Provide secondary development interface. SNMP (V1/V2C/V3).

4.2 Product size

JSY-MK-352 IP Intelligent PDU Dimensions.

ip pdu main board size

 JSY-MK-352AFE  Three-phase four-wire power module dimensions

PDU power board size

JSY1073 single-phase power module dimensions

PDU power board size

 JSY1054 4-channel relay control module dimensions

PDU relay control board size

 JSY1084 4-channel relay control module dimensions

relay board size
  1. 5. WEB Network Operation

 5.1 Supported browsers

  • You can access the PDU through its web interface using IE, Google 360, or Microsoft Edge . Other commonly used browsers may work but have not been fully tested.

5.2 Cascade Setting Instructions

  • ◆ You can use the PDU's system IP address as the URL of the web interface and log in using a case-sensitive username and password.
  • ◆ The PDU uses a static IP address by default when it leaves the factory. The default address is 192.168.1.190. The current IP address can be queried from the network status page on the LCD display of the display module. If you need to configure a dynamic IP, you need to enable the DHCP function of the device.
  • ◆ Before using the cascading function, you need to select the master-slave mode for each PDU configuration. The master mode has only one PDU, and the slave mode can be configured with 4 PDUs by default .

5.2.1 Cascade settings

  • After the PDU is powered on, plug the network cable into its network port. At this time, in the LCD display of the display module, by short pressing the button, you can query the IP address from the host information, as shown in the figure 192.168. 1 .1 90.
web interface 1
web interface 2
web interface 3
web interface 5

Post time: Feb-14-2025